Hochiki YBO-BS Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Audio Hochiki YBO-BS. Hochiki YBO-BS User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 3
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
2-3-0-629/ISS3/JUN11
HOCHIKI YBO-BS BASE SOUNDER
INSTALLATION INSTRUCTIONS
Products Covered: YBO-BS installed with ALG-E, ALG-E(NP), AIE-E, AIE-E(NP), ATG-E,
ATG-E(NP), ACA-E, ACB-E Sensors, CHQ-AB Range of Beacons, CHQ-ARI Remote Indicator and
YBN-R/3 Standard Base, YBO-R/SCI Short-Circuit Isolator Base (from batch code 6044 only).
Introduction
The Loop-Powered Sounder Base (YBO-BS) is designed to complement the standard common mounting base
(YBN-R/3) and the isolator base (YBO-R/SCI) in locations where Loop-Powered Sounders are required. The YBO-
BS has connections for both of these types of base as well as for the standard range of Hochiki Analogue
Addressable Sensors and Beacons. The YBO-BS is designed to give audibility in locations such as Hotel
Bedrooms, Offices and Corridors. Note that the YBO-BS is for indoor use only (Type A) and is rated at IP21.
Fig. 1
Common Configurations
The YBO-BS can be used in conjunction with an ESP Sensor, Beacon or Remote
Indicator (see Fig.1) or with the addition of a Cap (see Fig. 2).
Address Setting
The default address of the YBO-BS is 254, and therefore if the YBO-BS is to be
used as a base sounder (sensor on top) then the address will not need to be
changed, as the control panel will automatically address the sounder as described
below. However, if the sounder is to be used as a wall sounder then the YBO-BS
will need to be manually addressed from 1 to 127 as described below. Note:
Control Panel compatibility needs to be checked to verify if automatic
addressing above 127 is supported.
Automatic Addressing (Control Panel)
The control panel automatically assigns the address to the base sounder at
initialisation, the address is calculated by taking the address of the sensor that is
fitted to the base sounder and adding 127, this is then stored within the base
sounder. For example, if a sensor is set at address 10 then the base sounder
would be automatically set at address 137. Addresses above 127 may not be
visible to the user depending upon the implementation by the Control Panel.
Fig. 2
Manual Addressing (Hand Held Programmer)
The base sounder address can be set using the Hand Held programmer (TCH-B100) from 1 to 254. See the TCH-
B100 instructions for further details of address setting. If the YBO-BS is to be used as a wall sounder then the
address should be set from 1 to 127 before being installed. If the YBO-BS is to be used as a base sounder
(sensor on top) then the address should be set from 128 to 254.
Precautions
Ensure that the base sounder is installed in accordance with Local Standards or Regulations.
Check that both sensor and mounting base are compatible with the YBO-BS.
Only install in suitable environments, the following in particular should be avoided: -
Excessive ambient temperature.
Where excessive condensation or moisture is present.
Hazardous areas.
A high voltage tester must not be used with this base sounder.
Ensure that the base sounder is securely fixed to the mounting base.
For proper wiring supervision ensure that the cables are wired as shown in the diagram below.
Vue de la page 0
1 2 3

Résumé du contenu

Page 1 - INSTALLATION INSTRUCTIONS

2-3-0-629/ISS3/JUN11 HOCHIKI YBO-BS BASE SOUNDER INSTALLATION INSTRUCTIONS Products Covered: YBO-BS installed with ALG-E, ALG-E(NP), AIE-E, AIE-E(

Page 2 - Locking Mechanism

2-3-0-629/ISS3/JUN11 Tones and Volumes Table 1 below shows the full range of sound outputs available from the YBO-BS and the amount of current draw

Page 3

2-3-0-629/ISS3/JUN11 Wiring Please refer to the following diagrams for wiring the Standard Mounting Base (YBN-R/3) and the Short-Circuit Isolator M

Commentaires sur ces manuels

Pas de commentaire